ON OTOMASYON - Schneider Sensors Catalogue - page 24

CAT-SENSORS-EU.BU.N.EN.2.2012.0.01.CC
24
Temperature
Sensors
STT
Frost Thermostats
STT900
The frost protection thermostat STT is used for air, or water-side temperature
monitoring of heat exchangers, hot water circulation systems, water / air
heaters, e.g. in ventilation and air conditioning systems and for the prevention
of frost damage. The product features a small operating differential and high
reproducibility. Resetting of the STT900 to STT904 occurs automatically, and the
STT910-STT914 are designed to be reset manually by a reset button.
The output would typically switch off ventilators, close outside air flaps, open up
air heating valves, switch on air heat pumps, switch off refrigeration compressors,
switch off air humidifiers, or initiate a visual and / or acoustic frost alarm.
Location of these items in not critical, even in harsh environments as they are all
rated to IP65.
Part
number
Model
number
Description
Length of capillary
Control
characteristics
Permissible
medium
5127090000 STT910 STT910 Frost Stat M 0,6m Manual
Air
5127080000 STT914 STT914 Frost Stat M 12m Manual
Air
5127070000 STT912 STT912 Frost Stat M 3m Manual
Air
5127060000 STT911 STT911 Frost Stat M 1,8m Manual
Air / Water
5127050000 STT913 STT913 Frost Stat M 6m Manual
Air
5127040000 STT900 STT900 Frost Stat A 0,6m Automatically
Air
5127030000 STT904 STT904 Frost Stat A 12m Automatically
Air
5127020000 STT902 STT902 Frost Stat A 3m Automatically
Air
5127010000 STT901 STT901 Frost Stat A 1,8m Automatically
Air / Water
5127000000 STT903 STT903 Frost Stat A 6m Automatically
Air