ON OTOMASYON - HK INSTRUMENTS Catalogue - page 17

17
TECHNICAL DETAILS
Communication:
RS-485 Modbus (RTU)
Accuracy from range:
±1,5% (±6Pa <250 Pa)
(including: general accuracy, temperature drift, linearity, hysteresis and repetition error)
Long term stability, typical 1 year:
• ± 1 Pa with AZ,
• ± 8 Pa without AZ; model 2500
• ± 24 Pa without AZ; model 7000
Zero point adjustment:
via Modbus or by push button, automatic with optional autozero element (-AZ)
Supply voltage:
24 VDC ±10 % / 24 VAC ±10 %
Power consumption:
< 1.3 W
Output signal:
via Modbus (RTU)
Ambient temperature:
-10…+50 °C
Response Time:
0,8 / 2 / 10 s
Protection standard:
IP54
DPT-MOD
Code
Product description
Measuring range (Pa)
114.001.001
DPT-MOD 2000
0…100/250/500/1000/2000
114.002.001
DPT-MOD 5000
0…1000/2000/3000/5000
114.001.006 DPT-MOD-2000-AZ
0…100/250/500/1000/2000
114.002.004 DPT-MOD-5000-AZ
0…1000/2000/3000/5000
Dimensions
ACCESSORIES
SEE PAGE 50
!
"
#
!
$
!
"
#
$
%
$
#
&
%
&
#
&
'
(
#
&
!
!
#
&
$
'
#
&
)
)
)
)
*
#
'
+
+
1...,7,8,9,10,11,12,13,14,15,16 18,19,20,21,22,23,24,25,26,27,...56