Accuracy:
Range 0…2 m/s <0,1m/s +5% from reading
Range 0…10 m/s <0,5m/s +5% from reading
Range 0…20 m/s <1,0m/s +5% from reading
Supply voltage:
24 VDC ±10% / 24 VAC ±10%
Power consumption:
35mA (50mA with relay) + 40mA with mA outputs
Output signal 1:
0…10V (linear to ºC), L min 1k! or
4…20mA (linear to ºC), L max 400!
Output signal 2:
0…10V (linear to m/s), L min 1k! or
4…20mA (linear to m/s), L max 400!
Optional relay output:
Potential free SPDT 250VAC, 6A / 30VDC,
6A with adjustable switching point and hysteresis
Ambient temperature:
0…+50 °C
Probe:
Adjustable Immersion length 50...190mm,
mounting flange included
Protection standard:
IP54
AVT
Product code
Product description
Measuring range (Pa)
117.004.001 AVT 0…2 / 0…10 / 0…20 m/s
117.004.002 AVT-D 0…2 / 0…10 / 0…20 m/s
117.004.003 AVT-R 0…2 / 0…10 / 0…20 m/s
Dimensions
Dimensions of probe
!
"
#
$
%
&
!
"
#
$
!
$
#
$
!
"
#
$
%
&
#
$
'
"
#
$
(
$
#
$
'
"
#
$
)
'
$
#
$
*
*
*
*
'
$
#
$
+
+
ACCESSORIES