56
CAT-SENSORS-EU.BU.N.EN.2.2012.0.01.CC
Appendix A:
Sensor Accuracy Tables
Table E
For all Andover Continuum Averaging Sensors (500 Series),
e.g. STD500-150
At temperature
Accuracy
-25 °C/-13 °F
±0.5 °C/±0.9 °F
±0 °C/32 °F
±0.2 °C/±0.4 °F
25 °C/77 °F
±0.2 °C/±0.4 °F
50 °C/122 °F
±0.2 °C/±0.4 °F
70 °C/158 °F
±0.2 °C/±0.4 °F
100 °C/212 °F
±0.5 °C/±0.9 °F
Table F
For all Satchwell Sensors (600 Series), e.g. STR600
At temperature
Accuracy
-25 °C/-13 °F
±0.6 °C/±1.0 °F
±0 °C/32 °F
. ±0.3 °C/±0.5 °F
25 °C/77 °F
±0.2 °C/±0.4 °F
50 °C/122 °F
±0.2 °C/±0.4 °F
75 °C/167 °F
±0.3 °C/±0.5 °F
100 °C/212 °F
±0.3 °C/±0.5 °F
Table G
For STR800 Living Space Sensors
At temperature
Accuracy
0°C/32°F
±0.3°C/±0.5°F
10°C/50°F
±0.3°C/±0.5°F
25°C/75°F
±0.3°C/±0.5°F
35°C/95°F
±0.3°C/±0.5°F
50°C/122°F
±0.3°C/±0.5°F
Table A
For all TAC Vista (100 Series Sensors), e.g. STD100
At temperature
Accuracy
-25 °C/-13 °F
±0.7 °C/±1.3 °F
±0 °C/32 °F
±0.5 °C/±0.9 °F
25 °C/77 °F
±0.3 °C/±0.5 °F
50 °C/122 °F
±0.6 °C/±1.1 °F
75 °C/167 °F
±0.9 °C/±1.6 °F
100 °C/212 °F
±1.3 °C/±2.3 °F
Table B
For all TAC I/NET (200 Series Sensors), e.g. STD200
At temperature
Accuracy
-25 °C/-13 °F
±0.5 °C/±0.9 °F
±0 °C/32 °F
±0.2 °C/±0.4 °F
25 °C/77 °F
±0.2 °C/±0.4 °F
50 °C/122 °F
±0.2 °C/±0.4 °F
70 °C/158 °F
±0.2 °C/±0.4 °F
100 °C/212 °F
±0.5 °C/±0.9 °F
Table C
For all Andover Continuum (500 Series Sensors), e.g. STD500
At temperature
Accuracy
-25 °C/-13 °F
±0.5 °C/±0.9 °F
±0 °C/32 °F
±0.2 °C/±0.4 °F
25 °C/77 °F
±0.2 °C/±0.4 °F
50 °C/122 °F
±0.2 °C/±0.4 °F
70 °C/158 °F
±0.2 °C/±0.4 °F
100 °C/212 °F
±0.5 °C/±0.9 °F
Table D
For all TAC Vista Averaging Sensors (100 Series), e.g.STD 190
At temperature
Accuracy
-25 °C/-13 °F
±0.7 °C/±1.3 °F
±0 °C/32 °F
±0.5 °C/±0.9 °F
25 °C/77 °F
±0.3 °C/±0.5 °F
50 °C/122 °F
±0.6 °C/±1.1 °F
75 °C/167 °F
±0.9 °C/±1.6 °F
100 °C/212 °F
±1.3 °C/±2.3 °F